Customization: | Available |
---|---|
Type: | Water-Cooled |
Cooling Method: | Water-cooled |
Suppliers with verified business licenses
Flooded Type Water Cooled Screw Chiller
The water-cooled screw flooded chiller is a powerful, efficient, and durable cooling solution for large-scale applications. Its use of water in both the evaporator and condenser circuits helps optimize heat exchange, making it a highly efficient system for industrial and commercial purposes.
A water-cooled screw flooded chiller is a type of industrial cooling system that utilizes a screw compressor and water for heat dissipation. It's widely used in large commercial buildings, industrial processes, and air conditioning systems. Here's a breakdown of its key components and working principles:
Screw Compressor:
The screw compressor is the heart of the system, consisting of two helical rotors (male and female screws). As these screws rotate, they compress the refrigerant gas, increasing its pressure and temperature.Flooded Evaporator:
In a flooded evaporator, the refrigerant is in direct contact with the cooling water. The refrigerant absorbs heat from the water, lowering the water's temperature. This design ensures that most of the evaporator surface is used for heat exchange, increasing efficiency.Condenser:
The water-cooled condenser transfers the heat from the refrigerant to the cooling water. Typically, a separate cooling tower is used to expel this heat to the atmosphere, which allows the refrigerant to condense back into a liquid.Expansion Valve:
The expansion valve regulates the flow of refrigerant entering the evaporator. It drops the refrigerant's pressure, turning it into a low-pressure, low-temperature mixture before it absorbs heat in the evaporator.Cooling Water Circuit:
This system uses a water loop to remove heat from the condenser. The water flows to a cooling tower where it releases the absorbed heat to the surrounding air.Compression:
The refrigerant gas enters the screw compressor, where it's compressed to a high pressure and temperature.Condensation:
The hot, pressurized gas moves to the condenser. Water from the cooling tower passes through the condenser coils, absorbing heat from the refrigerant. As the heat dissipates, the refrigerant condenses into a high-pressure liquid.Expansion:
The liquid refrigerant passes through the expansion valve, where its pressure and temperature drop significantly, preparing it to absorb heat.Evaporation:
In the flooded evaporator, the refrigerant comes into contact with water, absorbing its heat. This cools the water for recirculation in the air conditioning or industrial cooling process. The refrigerant, in turn, evaporates into a gas.Recycling:
The low-pressure refrigerant gas returns to the compressor, and the cycle begins again.Model PCWF | 1080B | 1100B | 1120B | 1150B | 1180B | 1200B | 1220B | 1255B | 1270B | |||
Cooling Capacity | kW | 275 | 345 | 416 | 525 | 630 | 680 | 768 | 892 | 957 | ||
kcal/h | 236500 | 296700 | 357800 | 451500 | 541800 | 584800 | 660500 | 767100 | 823000 | |||
Input Power | kW | 52.5 | 63.5 | 77.4 | 96 | 115.9 | 124 | 138 | 157.6 | 172.8 | ||
Rated Current | A | 96 | 118 | 138 | 171 | 208 | 217 | 252 | 279 | 305 | ||
Power Supply | 380V/3N-/50Hz | |||||||||||
Capacity Regulating | 25%-100% | |||||||||||
Compressor | Type | 5-6 Unmatching Gear Type Semi Hermetic Screw Compressor | ||||||||||
Starts Up | Y- | |||||||||||
Qty | Set | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |||
Oil Heater | W | 300 | ||||||||||
Evaporator | Type | High Efficiency Flooded Type Heat Exchanger | ||||||||||
Water Flow Rate | m3/h | 47 | 59 | 72 | 90 | 108 | 117 | 132 | 153 | 165 | ||
Pressure Drop | kPa | 45 | 45 | 45 | 48 | 78 | 78 | 81 | 78 | 77 | ||
Connecion Pipe | DN | 100 | 100 | 100 | 125 | 125 | 125 | 150 | 150 | 150 | ||
Condenser | Type | Shell and Tube Heat Exchanger | ||||||||||
Water Flow Rate | m3/h | 59 | 74 | 89 | 113 | 135 | 146 | 165 | 192 | 206 | ||
Pressure Drop | kPa | 50 | 52 | 52 | 55 | 80 | 80 | 80 | 80 | 80 | ||
Connecion Pipe | DN | 100 | 100 | 125 | 125 | 150 | 150 | 150 | 150 | 150 | ||
Refrigerant | Type | R22 | ||||||||||
Charged | kg | 100 | 115 | 115 | 120 | 175 | 175 | 160 | 205 | 205 | ||
Dimension | Length | mm | 3100 | 3100 | 3100 | 3000 | 3650 | 3650 | 3550 | 3600 | 3600 | |
Width | mm | 1120 | 1120 | 1260 | 1260 | 1350 | 1350 | 1400 | 1500 | 1500 | ||
Height | mm | 1700 | 1700 | 1800 | 1850 | 1950 | 1950 | 2000 | 2050 | 2050 | ||
Weight | Transporation Weight | kg | 2400 | 2550 | 2800 | 3100 | 3500 | 3550 | 3600 | 4000 | 4000 | |
Operation Weight | kg | 2550 | 2700 | 3000 | 3300 | 3750 | 3800 | 3850 | 4300 | 4300 |
At Central Air Conditioning Solutions, Umbrellaclimate specialize in delivering top-tier climate control systems designed to enhance the comfort, efficiency, and sustainability of homes, businesses, and industrial spaces. With over 40 years of experience in the HVAC (Heating, Ventilation, and Air Conditioning) industry, we are a trusted partner for high-quality central air conditioning systems.